SPDT manual reset high limit, adjustable limiter
Housing dimensions: 79 x 53 x 36 mm (without terminals)
Bulb and capillary: Copper for temperature ranges up to 50°C(120°F), stainless steel above ,capillary length 1500 mm or 3000 mm.
Electrical rating | |
---|---|
Temperature adjustment range (°C) | -25/+25, 0/50, 0/70, 10/150, 10/450, 20/90, 50/300, 60/500, 80/200, 180/600, 280/700 |
Capillary length (mm) | |
Bulb diameter (mm) | |
Bulb length (mm) | |
Differential (°C) | |
Max temperature on bulb (°C) |
Description
TECHNICAL FEATURES
Housing dimensions: 79 x 53 x 36 mm (without terminals)
Bulb and capillary: Copper for temperature ranges up to 50°C(120°F), stainless steel above ,capillary length 1500 mm or 3000 mm. Capillary minimum bending radius 5mm.
Temperature sensing element: Liquid filled bulb and capillary.
Terminals: 6.35 x 0.8 quick connect terminals (M4 screws also available on request),
Adjustment: Dia. 6 mm shaft with 4.6 mm flat, (other lengths or fixed setting available on request).
Mounting: Front bracket with 2 xM4 threads, 28 mm distance
Rating: 15A (1/4 HP) 250VAC, 15A 400V res.
Contacts: SPDT (snap action contact)
Electrical life: >100.000 cycles at nominal rating
Main references
Reference |
Temperature range (°C/°F) | Capillary length (mm) | Bulb diameter (mm) | Bulb length (mm) | Reset Differential (°C/°F) | Max temperature on bulb (°C/°F) |
KXC-250252200 | -25+25°C (-15+80°F) | 1500 | 6.4 | 152 | 6±2°C/42.8±35.6°F | 50°C (120°F) |
KXC-1001552000 | -10+15°C (15-60°F) | 1500 | 6.4 | 152 | 6±2°C/42.8±35.6°F | 50°C (120°F) |
KXC0000502000 | 0-50°C (32-120°F) | 1500 | 6.4 | 152 | 6±2°C/42.8±35.6°F | 60°C (140°F) |
KXC0000705200 | 0-70°C (32-160°F) | 1500 | 4.8 | 120 | 10±3°C/50±37.4°F | 160°C (320°F) |
KXC0000701200 | 0-70°C (32-160°F) | 3000 | 4.8 | 120 | 10±3°C/50±37.4°F | 160°C (320°F) |
KXC0200905000 | 20-90°C (70-195°F) | 1500 | 4.8 | 120 | 10±3°C/50±37.4°F | 160°C (320°F) |
KXC0200901000 | 20-90°C (70-195°F) | 3000 | 4.8 | 120 | 10±3°C/50±37.4°F | 160°C (320°F) |
KXC0101505000 | 10-150°C (50-300°F) | 1500 | 4.8 | 120 | 10±3°C/50±37.4°F | 160°C (320°F) |
KXC0101501000 | 10-150°C (50-300°F) | 3000 | 4.8 | 120 | 10±3°C/50±37.4°F | 160°C (320°F) |
KXC0802000100 | 80-200°C (175-390°F) | 1500 | 4 | 100 | 20±4°C/68±39.2°F | 320°C (610°F) |
KXC0503000100 | 50-300°C (120-570°F) | 1500 | 4 | 100 | 20±4°C/68±39.2°F | 320°C (610°F) |
KXC0104507000 | 10-450°C (50-840°F) | 1500 | 4.8 | 120 | 40±6°C/104±42.8°F | 760°C (1400°F) |
KXC0104509000 | 10-450°C (50-840°F) | 3000 | 4.8 | 120 | 40±6°C/104±42.8°F | 760°C (1400°F) |
KXC0605007000 | 60-500°C (140-930°F) | 1500 | 4.8 | 120 | 40±6°C/104±42.8°F | 760°C (1400°F) |
KXC0605009000 | 60-500°C (140-930°F) | 3000 | 4.8 | 120 | 40±6°C/104±42.8°F | 760°C (1400°F) |
KXC1806007000 | 180-600°C (360-1110°F) | 1500 | 4.8 | 120 | 40±6°C/104±42.8°F | 760°C (1400°F) |
KXC1806009000 | 180-600°C (360-1110°F) | 3000 | 4.8 | 120 | 40±6°C/104±42.8°F | 760°C (1400°F) |
KXC2807008000 | 280-700°C (540-1290°F) | 1500 | 3 | 300 | 40±6°C/104±42.8°F | 760°C (1400°F) |
Caution: Bulbs and capillaries of ranges higher than 300°C are filled with sodium potassium eutectic. If they leak or are broken this liquid is flammable if in contact with water
Downloads
TO ACCESS DOWNLOAD DOCUMENTS, PLEASE LOGIN/REGISTER. DATASHEET, DRAWINGS (.DWG), 3D MODELS (.STP) AND OTHER DOCUMENTS ARE AVAILABLE.RELATED PRODUCTS
-
Manual reset electronic adjustable limiter, remote sensor, IP65
Applications Temperature high limit, in usual industrial application and environment, non-hazardous areas. Internal adjustment is convenient for products that must not be frequently adjusted. Use of electronic sensor allows measurement at long distances, which is not possible with bulb and capillary types.
-
Adjustable manual reset electronic room limiter IP66, IK10
- Equipment requesting a very strong resistance to water ingress. The transparent cover allows to visualize the set point and the 2 pilot lights. Wall mounting for indoor or outdoor high temperature alarm of cold High temperature alarm of industrial or commercial Outdoor temperature alarm of antifreeze High temperature alarm of green houses and livestock
SIMILAR PRODUCTS
-
Adjustable manual reset electronic rod limiter IP66, IK10
- Equipment requesting a very strong resistance to water ingress. The transparent cover allows to visualize the set point and the 2 pilot lights. These electronic rod thermostats are installed inside pockets as immersion thermostats in pipelines and containers, and for monitoring temperature in air ducts. - Manual reset allows the use as high temperature…
-
Manual reset electronic rod limiter, IP65
Applications These rod limiters with electronic sensor with adjustable set point can be installed inside pockets as immersion high temperature limits on pipelines and containers, and for monitoring temperature in air ducts, in usual industrial applications and environments. (Not suitable for hazardous areas). Internal adjustment is convenient for products that must not be frequently adjusted.
-
Electronic thermostat, multi range, control and manual reset action, for incorporation, NTC sensor
This electronic thermostat for incorporation has been designed to replace electromechanical thermostats. It is mounted with two screws M4 at the same distance 28 mm, uses a 6mm dia. shaft with 4.6mm flat with the same length, and its rotation angle is 230°. Therefor temperature ranges are quite the same as the bulb and capillary…
Technical informations associated to this product
-
Description of temperature controls
Used as control thermostats or as a safety thermostat with manual reset, these thermostats have a disc made of two different metals laminated together for temperature sensing element. These two metals have different expansion coefficients. -
Thermostats installation
The proper functioning of a thermostat depends primarily on the correct choice of the component, but also the conditions of its installation. Conditions used to calibrate regulating and control equipment in the factory are always ideal laboratory conditions, ensuring measurement accuracy and repeatability. These conditions are rarely those found in practice when installing thermostats. However, with a minimum of constraints, it is possible to optimize assemblies. -
Electrical contacts
As numerous mechanisms exist, we decided not to distinguish on the basis of constructive technique, but according to their operation speed, which is the key element. -
Electrical protection classes
The housings are designed to protect electrical equipment located inside. This protection must be considered in the electrical and environmental angles.)