40 attribut :
-
Copper fusible links with eutectic alloys, for medium loads
These fusible links have a medium response time, between 3 minutes 25 seconds and 3 minutes 30 seconds, for a temperature rise rate of 20°C/min from 25°C, and their thickness of metal is thicker than brass models to gives them sufficient strength for their use in multiplied mechanisms supporting a maximum stress of 300DaN. The…
-
Eutectic alloys fusible links for medium loads
These fusible links have a medium response time, between 3 minutes and 3 minutes 10 seconds, for a temperature rise rate of 20°C/min from 25°C and their thickness of metal gives them sufficient strength for their use in multiplied mechanisms supporting a maximum load of 300DaN. The holes have a lip to improve their resistance…